In this age of automation, process control in
the process industries is essential. Every piece of process equipment is
outfitted with automatic control to operate without human intervention and a
safe shutdown in the event of an upset. The basic process control system (BPCS)
and the safety instrument system (SIS) are used to configure this automation.
As a result, every process engineer should be familiar enough with the process
control to detect and troubleshoot any control issues. Consequently, process
control engineers who understand both the process and the control system are
now required.
This article will detail a fundamental process
control system that is not based on the Laplace transform. Here, some features
of an ideal controller are provided, as well as how process engineers should
check these control systems during piping and instrumentation diagram (P&ID)
review and execution.
Power and motive fluid failure. Control valves are the last control
element in all industries, particularly the process industry. These control
valves have a fail-safe mode that is determined by the safety of the equipment
as well as the plant—this
can be a fail to open, close or lock. However, the fail-safe position differs
depending on whether the power or motive fluid fails. In the event of a motive
fluid failure such as instrument air or control oil, the control valve will
remain in the fail-safe position while power is still available. The control
valve positioner will then get output based on the controller output; once the
motive fluid is available, the control valve will receive the same position
based on output.
When motive fluid is available but there is
only a power failure—while
backup power is generally available, a total blackout situation is considered
here—all
controllers enter into manual mode by default and the output (mill ampere) that
goes from controller to positioner becomes zero (not 4 milliamps), and the
control valve sees the zero milliamps and goes to a fail-safe position as a
result.
The two cases appear to be the same. In both
cases, the control valve enters fail-safe mode. However, the fail-safe design
is exclusively dependent on motive fluid failure, and the valves operate owing
to 0 milliamps upon power loss. This does not imply that the two cases are
identical. As previously indicated, 95% of control valves operate similarly in
both circumstances, but the remainder behave differently (fail-safe in motive
fluid failure and in power failure, valves hold the same position or just
opposite to motive fluid failure).
Synchronous proportional, integral,
derivative (PID). The scan time of any
controller is the amount of time it takes to calculate the output based on the
input error. In general, the controller calculates the error (set point–process
valve) and then modifies the output based on that error. This output is sent as
current (milli amps) to the final control element (in the process industry, a
control valve) (4 mA–20
mA). The frequency of the controller is referred to as the “scan time of the
controller.” Conversely, the scan frequency of any measurement element of a
measuring sensor varies depending on the process.1
Although pressure and flow sensors are slightly
faster and temperature and composition (analyzer) measuring sensors, depending
on the process design, have a long reaction time and dead time. Analyzers are
frequently multiplexed with a large number of streams to detect with a single gas
chromatography (GC) instrument and to save money on capital. The measurement
period of a single stream is extended by minutes to half an hour. Each
measuring sensor has its own transfer function, as well as its own reaction and
scan time.
The measured value is sent into the controller as a process value (PV), and the setpoint is determined by an operator or another controller. The controller's scan time and the response time of measuring sensors should be identical and synchronized to avoid process disturbance. If the controller is faster than the measuring element's response time, the controller calculated output can travel a long distance using old values. Some plants utilize asynchronous controllers, which compute the output based on the old PV value rather than the new PV value. The process is disrupted by this type of asynchronous controller, and the controller is run manually by the operator.
Slew rate. This is the rate at which the controller's output
changes over time. Although a controller's output (MV) can be altered in
milliseconds to seconds (depending on scan time), the ultimate control element
(control valve) is slow and can take minutes to open. When the controller is
faster than the final control valve response, the output is repeatedly
transmitted to the control valve that is not opening owing to the delayed reaction.
The controller output may exceed the required
opening, causing the process parameters to become unstable. In some
circumstances, the controller may also reach apex value. Some control valves in
plants operate in a separate fashion. When the controller's output is between 1%
and 5%, it does not act; when it exceeds 6%–10%, it quickly opens. This causes
the process parameters to be disrupted, forcing the controller to act in the
opposite direction. To avoid such problems, the slew rate of essential
controllers should be aligned with the control valve.
If the control valve is fast, the controller output
should be quick as well, and vice versa. These two characteristics prevent the
controller from turning on during normal operation. If the control valves are
at their limits (open or completely closed) and the controller still has an
error, the controller can compute output and increase until the error is zero.
The controller's output can exceed this limit, causing the controller to overrange.
To prevent wind-up, controllers have an anti-reset windup (ARW) feature that
locks the output computation when the final element is near the limit.
The following recommendations and best
practices to achieve smooth controlling can be used as check list:
ACKNOWLEDGEMENT
This
work is based on the author’s experience and learning and is not affiliated
with any company. The author is grateful to Shree Krishna for support and
advice during the writing of this article.
LITERATURE CITED
ABHISHEK SHARMA works at an ethylene plant as a Process Engineer and is actively involved in the plant's smooth running and troubleshooting. He has more than 4 yr of experience working in the steam cracker unit and earned his B.Tech degree in chemical engineering with honors from the National Institute of Technology Raipur in India. Sharma has also finished a process control course from IIT Mumbai and trained under the American Institute of Automation and Process Control (AIAPC). He is an associate member of the IChemE and an active professional member of the American Institute of Chemical Engineers. Sharma is the author of more than seven articles, case studies and papers.